Function
The purpose of filter driers is to keep the refrigeration circuit clean of solid contaminants, water and acid. Contamination can cause corrosion and ice building as well as malfunction of the compressor.
Liquid filter driers are especially designed for a high water capacity whereas suction line filter driers feature a high acid and filtration capacity.
     
  Property of Desiccants

Molecular sieves

This kind of desiccant has a very good drying effect
independent of the oil content of the refrigerant. Molecular
sieve is a fast acting desiccant and will remove moisture even
when the water content of the refrigerant is low and when the
temperature of the liquid refrigerant is high.

Activated alumina
Activated alumina incorporate an excellent acid and filtration
capacity. By selecting a specific mixture of both desiccants an
optimum effect can be achieved to cover the requirements of
all kinds of applications.
     
  Flow Capacity
Flow capacity refers to ARI-Standard 710-86 and is based on a pressure drop of 14 kPa, +30°C liquid temperature and -15°C evaporating temperature.
     
  Recommended Capacity
Recommended capacity applies to common installations with liquid temperatures to +30°C and evaporating temperatures above of -15°C. The next larger drier size should be selected for installation with lower evaporating temperatures, excessive pipe length, excessive refrigerant content or other. The next smaller drier size can be selected for factory assembled units and/or for higher evaporating temperatures.
     
  Water Capacity
The water capacity for R 22 refers to ARI 710-86 and is based on a liquid temperature of 24/52°C and a equilibrium point dryness (EPD) of 60 PPM water in refrigerant. The stated capacities for R 134a are at 60 PPM, for R 404A at 50 PPM.
     
 
 
Filter Driers Series EK-Plus
Hermetic Design, for Liquid Refrigerants
 
 

Optimum blend of molecula sieve and activated alumina

     
  High water and acid capacity
     
  Filtration down to 40 micron
     
  Temperature range -45°C to +65°C
     
  Maximum operating pressure 3100 kPa
 
 
 
 
Filter Driers Series ADK-Plus
Hermetic Design, for Liquid Refrigerants
 
 

Optimum blend of molecularsieve and activated alumina

     
  High water and acid capacity
     
  Filtration down to 40 micron
     
  Temperature range -45°C to +65°C
     
  Maximum operating pressure 3100 kPa