One Indicator for Refrigerants
12, 134a, 22, 404A, 502 and 507 |
| |
|
The See-All Moisture and Liquid Indicator
provides a true moisture indication for Refrigerants 12,134a,
22,404A, 502 and 507. The See-All is also suitable for Refrigerants
401A & B, 402 A & B, 408A and 409A. The dark green indicates
dry and a bright yellow indicates wet. The one indicator avoids
the confusion found in models with two elements. You cannot
pick the wrong element when checking the moisture content of
the system. |
|
| |
| |
| |
 |
Reliable and Accurately Calibrated
Colour Change Points |
| |
|
The See-All Moisture and Liquid Indicator
is accurately calibrated in parts per million of moisture for
each refrigerant. All moisture indicators change colour on the
basis of relative saturation of the refrigerant. Therefore,
liquid line temperature must be considered if an accurate calibration
is to be obtained. A colour chart is part of the label, for
easy comparison. |
|
| |
| |
| |
 |
Colour Changes Are Easily Distinguished
and Reverisble |
| |
|
The indicator's colour differs so
widely between WET and DRY conditions that there is no possibility
of confusion between the two. Colours will reverse as often
as moisture concentration in the system changes. |
|
| |
| |
| |
 |
Large Full View Sight Glass |
| |
|
The See-All Moisture and Liquid Indicator
has an extra large crystal clear sight glass for viewing the
refrigerant. Bubbles indicate a shortage of refrigerant or a
restriction in the liquid line. |
|
| |
| |
| |
 |
Indicator Protected from Discolouration
and Dirt |
| |
|
The indicator is protected by a filter
pad and screen. This prevents washing of the indicator by the
refrigerant and protects it from system contamination and turbulence. |
|
| |
| |
| |
 |
Replaceable Indicator Element |
| |
|
The colour indicator paper can be
changed on the new fused glass models without removing the See-All
from the line. Replacement is through the bottom (see SA-14SU
below). Request the K-SA-4 Kit. |
|
| |
| |
| |
 |
Disassembly of the Smaller Sizes
Not Required |
| |
|
The extended steel fittings on solder
models in the smaller sizes make it unnecessary to disassemble
for installation since steel conducts only one eighth as much
heat as copper. |
|
| |
| |
| |
 |
Double Duty Plastic Cap |
| |
|
A DOUBLE DUTY PLASTIC CAP is supplied
to keep the glass free from dust, dirt, and grease. It also
permits the service engineer to use his own discretion concerning
instructions to his customers on observing the See-All Moisture
and Liquid Indicator. |
|
| |
| |
|
|